← 返回
基于双极限齐次性的分布式二次控制用于受非均匀时延和执行器饱和影响的交流微电网
Distributed Secondary Control Based on Bi-Limit Homogeneity for AC Microgrids Subjected to Non-Uniform Delays and Actuator Saturations
| 作者 | Qingde Wang · Sunhua Huang · Linyun Xiong · Yang Zhou · Tao Niu · Fei Gao |
| 期刊 | IEEE Transactions on Power Systems |
| 出版日期 | 2024年4月 |
| 技术分类 | 储能系统技术 |
| 技术标签 | 储能系统 微电网 |
| 相关度评分 | ★★★★ 4.0 / 5.0 |
| 关键词 | 交流微电网 分布式二次控制 通信延迟 执行器饱和 功率共享 |
语言:
中文摘要
频率与电压是交流微电网中最关键的运行指标。针对存在非均匀通信时延和执行器饱和的交流微电网,本文提出一种基于双极限齐次性的分布式二次控制策略,实现频率恢复、平均电压调节及分布式电源间的有功与无功功率精确分配。通过引入基于历史控制输入的状态变换方法处理非均匀时延,并利用双曲正切函数逼近非光滑饱和特性,设计抗饱和固定时间控制器。结合构造的辅助双极限齐次系统,证明了闭环系统在执行器饱和约束下的固定时间稳定性。仿真结果表明,所提方法在频率/电压恢复及功率均分方面具有优越的鲁棒性与灵活性。
English Abstract
Frequency and voltage are the most significant indicators in AC microgrids (MGs). To maintain the stability of grid frequency and bus voltage, this paper proposes a distributed secondary control scheme based on bi-limit homogeneity for frequency restoration, average voltage recovery, active and reactive power sharing among DGs in AC MGs subjected to non-uniform communication delays and actuator saturations. First, a state-transformation-based strategy by virtue of the past information of the control input is designed to deal with non-uniform delays, which can fully alleviate the adverse effects of communication delays. Additionally, the hyperbolic tangent function is introduced to approximate the non-smooth saturation function and to design anti-saturation fixed-time controller, which can mitigate the impact caused by actuator saturations. Then, by constructing an auxiliary bi-limit homogeneous system, the fixed-time stability of the close-loop control system with the constraint of actuator saturation can be demonstrated. Finally, several simulation cases are conducted to evaluate the performance of the proposed strategy on a test MG system, and the results are compared with other existing methods. Simulation and comparison results reveal the proposed method's validity, robustness and flexibility in restoring the MG's frequency/average bus voltage and achieving accurate active/reactive power sharing.
S
SunView 深度解读
该双极限齐次性分布式控制技术对阳光电源PowerTitan储能系统和微电网ESS集成方案具有重要应用价值。针对多台ST系列储能变流器并联运行场景,该方法可有效解决通信网络非均匀时延和功率调节饱和问题,提升频率/电压恢复速度和功率均分精度。固定时间收敛特性可优化构网型GFM控制策略的暂态响应,抗饱和设计增强系统在极端工况下的鲁棒性。建议将该算法集成到iSolarCloud平台的分布式协调控制模块,提升大规模储能电站的二次调频性能和电压支撑能力,特别适用于通信条件受限的海外微电网项目。