← 返回
电动汽车驱动 构网型GFM 跟网型GFL ★ 5.0

跟网型与构网型逆变器负序行为的对比分析:建模、控制与保护

Comparative Analysis of Negative Sequence Behavior in Grid-Following and Grid-Forming Inverters: Modeling, Control, and Protection

作者 Xinquan Chen · Ilhan Kocar · Siqi Bu · Evangelos Farantatos · Aboutaleb Haddadi
期刊 IEEE Transactions on Power Delivery
出版日期 2025年4月
技术分类 电动汽车驱动
技术标签 构网型GFM 跟网型GFL
相关度评分 ★★★★★ 5.0 / 5.0
关键词 电网形成控制 逆变器 负序系统 故障穿越控制 负序阻抗
语言:

中文摘要

构网型(GFM)控制有望提升高比例逆变器并网系统的稳定性,但在电网不平衡条件下,其对负序电流幅值与相位的调节特性不同于跟网型(GFL)控制及同步发电机,可能违背故障穿越要求并导致保护误动。本文基于相量域解析模型,阐明GFL与GFM逆变器在负序系统中的基本特性及影响因素,提出一种简化的GFM逆变器阻抗计算方法,并实现适用于平衡正序控制(BPSC)与正负序控制(PNSC)的FRT控制策略。基于IEEE PSRC D29系统的对比研究表明,GFM BPSC方案下负序阻抗特性主要由内环电压控制参数决定,特定参数下可输出显著的负序无功电流,而IBR仍需依赖PNSC策略以实现负序响应的协调调控。

English Abstract

Grid-forming (GFM) controls are expected to enhance the stability of power systems with high penetration of inverter-based resources (IBRs). However, during unbalanced grid conditions, GFM controls alter the magnitude and angle of the negative sequence current contributed by IBRs, differing from grid-following (GFL) controls and synchronous generators. This behavior may not be in line with fault ride-through (FRT) requirements and cause maloperation of certain protection elements. This paper clarifies the fundamentals and impacting factors of GFL and GFM inverters in the negative sequence system using phasor-domain analytical models. A simplified impedance computation method for GFM inverters is proposed, and FRT control solutions for GFM and GFL inverters are implemented for balanced positive sequence control (BPSC) and positive and negative sequence control (PNSC) schemes. Comparative studies using the IEEE PSRC D29 system reveal that the magnitude and angle of negative sequence impedance are primarily determined by the inner voltage control parameters under the GFM BPSC scheme. Depending on the settings, GFM inverters can provide significant negative sequence reactive current under the BPSC scheme as opposed to GFL inverters. On the other hand, IBRs should still rely on PNSC strategies to regulate the negative sequence system response appropriately and in coordination.
S

SunView 深度解读

该研究对阳光电源ST系列储能变流器和SG系列光伏逆变器的GFM/GFL控制策略优化具有重要价值。文中提出的简化GFM阻抗计算方法可直接应用于PowerTitan储能系统的电网适应性设计,帮助优化内环电压控制参数以满足不平衡故障穿越要求。BPSC与PNSC控制策略对比为阳光电源构网型产品在弱电网场景下的负序电流调控提供理论依据,可避免保护误动风险。建议在iSolarCloud平台集成负序阻抗特性监测功能,并在1500V光伏系统和大型储能项目中验证PNSC策略的协调控制效果,提升高比例新能源并网系统的稳定性与合规性。