← 返回
储能系统技术 储能系统 多电平 ★ 5.0

基于时域偏度与积分能量的柔性直流配电网极对地故障保护方案

Pole-to-Ground Fault Protection Scheme for Flexible DC Distribution Network Based on Time Domain Skewness and Integral Energy

作者 Xiaowei Wang · Ying Tian · Jie Gao · Xiangxiang Wei · Fan Zhang · Yu Zhang
期刊 IEEE Transactions on Power Delivery
出版日期 2025年6月
技术分类 储能系统技术
技术标签 储能系统 多电平
相关度评分 ★★★★★ 5.0 / 5.0
关键词 多端柔性直流配电网 接地故障 保护方法 零模电流 故障识别
语言:

中文摘要

针对基于模块化多电平换流器的多端柔性直流配电网,线路故障若未能及时切除,将导致电力电子器件损坏甚至换流站烧毁。现有方法难以准确区分区内高阻故障与区外低阻故障。本文分析了系统发生接地故障时各测量点零模电流在时域与复频域的等效模型与方程,提出一种基于时域偏度与积分能量的接地保护方法。利用各测点零模电流偏度符号表征方向特性,线路积分能量表征幅值特性,结合两者可有效识别极端长线路条件下的故障特征。最后在PSCAD/EMTDC平台搭建四端柔性直流电网模型,验证了该保护方法的适应性与优越性。

English Abstract

For the multi terminal flexible DC distribution network based on modular multilevel converters, if the line fails and is not cut off in time, it will damage power electronic devices and may burn out the converter station. It is difficult to accurately distinguish between internal high resistance faults and external low resistance faults when faults occur in multi terminal flexible DC distribution networks. Analyzed the equivalent model and equation of zero-mode current at each measurement point in the time domain and complex frequency domain when a grounding fault occurs in the system. Based on this, a flexible DC distribution network grounding protection method based on time domain skewness and integral energy is proposed. Using the zero-mode current skewness symbol at each measuring point to characterize directional characteristics, and the integrated energy of the line to characterize amplitude characteristics. Using integrated energy as a supplement to skewness criteria can accurately extract fault features and perform fault identification in extreme cases where a certain line is long. Finally, a four-terminal flexible DC power grid model was built on the PSCAD/EMTDC simulation platform to verify the adaptability and superiority of the protection method.
S

SunView 深度解读

该柔性直流配电网保护技术对阳光电源ST系列储能变流器及PowerTitan大型储能系统具有重要应用价值。基于MMC拓扑的储能系统在直流侧故障时面临功率器件损坏风险,文章提出的时域偏度与积分能量双判据方法可有效解决高阻故障识别难题,适用于阳光电源多端直流储能并网场景。该保护算法可集成至ST系列产品的DSP控制器,实现毫秒级故障检测与隔离,提升SiC/GaN功率模块的安全裕度。同时为iSolarCloud平台的智能诊断功能提供故障特征数据库支撑,增强大型储能电站的预测性维护能力,降低极端工况下的设备损毁风险。